Products
PRODUCTS CENTER
Dou: 8615662585235
Meng: 8615853686124
Mail: dx@wfcooling.com
Address: North of the intersection of North Ring Road and West Ring Road, Weifang Economic Development Zone, Shandong
ML- FMT open cooling tower
Manufacturing of cooling tower shell with fiber reinforced materials, the general selection of coarse diameter in alkali glass fiber yarn woven square cloth, thickness from 0.2 to 0.8mm. The glass fiber surface needs to be coupled. It is strictly forbidden to use high-alkali glass fiber cloth produced by soil crucible. In order to improve the appearance quality, the surface is made of glass fiber surface felt with high resin content.
Key words:
Classification:
All-steel open tower
Tel:
Tel:
ML- FMT open cooling tower
Product Details
Manufacturing of cooling tower shell with fiber reinforced materials, the general selection of coarse diameter in alkali glass fiber yarn woven square cloth, thickness from 0.2 to 0.8mm. The glass fiber surface needs to be coupled. It is strictly forbidden to use high-alkali glass fiber cloth produced by soil crucible. In order to improve the appearance quality, the surface is made of glass fiber surface felt with high resin content.
The hot water autonomous machine room presses the circulating water into the water distribution system of the cooling tower through the pipeline, horizontal throat, curved throat and central throat under a certain pressure through the water pump, and evenly spreads the water on the packing through the small holes on the water distribution pipe. Dry air with low Han value enters the air network from the bottom into the tower under the action of the fan. When the hot water flows through the surface of the packing, a water film is formed for heat exchange with the air.
|
Model |
流量(m³/h) |
Working flow (m³/h) |
Inlet and outlet pipe diameter |
Fan |
Host size (mm) |
||||||
|
Wet bulb = 27 ℃ |
Wet bulb = 28 ℃ |
Power (kw) |
Diameter (mm) |
Number of blades |
Air volume (m³/h) |
Long |
Wide |
High |
|||
|
FMT-50 |
50 |
40 |
50 |
80 |
1.5 |
920 |
4 |
21000 |
1600 |
1600 |
2400 |
|
FMT-50W |
1560 |
1560 |
2100 |
||||||||
|
FMT-80 |
80 |
65 |
80 |
100 |
3.0 |
1500 |
4 |
32100 |
2250 |
2250 |
2775 |
|
FIMT-80W |
2060 |
2060 |
2505 |
||||||||
|
FMT-100 |
100 |
80 |
100 |
125 |
4.0 |
1800 |
4 |
61000 |
2750 |
2750 |
2810 |
|
FMT-100W |
2560 |
2560 |
3400 |
||||||||
|
FMT-150 |
150 |
130 |
150 |
100*2 |
3.0*2 |
1500 |
4 |
64600 |
4250 |
2550 |
2775 |
|
FMT-150W |
4060 |
2060 |
2505 |
||||||||
|
FMT-200 |
200 |
160 |
200 |
125*2 |
4.0*2 |
1800 |
4 |
112000 |
5250 |
2750 |
2810 |
|
FMT-200W |
5060 |
2560 |
5475 |
||||||||
|
FMT-250 |
250 |
200 |
250 |
100*3 |
30*3 |
1500 |
4 |
134300 |
6250 |
2250 |
2775 |
|
FMT-250W |
6060 |
2060 |
2505 |
||||||||
|
FMT-300 |
300 |
250 |
300 |
125*3 |
4.0*3 |
1800 |
4 |
168000 |
7750 |
2750 |
2810 |
|
FMT-300W |
7560 |
2560 |
2540 |
||||||||
|
FMT-400 |
400 |
350 |
400 |
124*4 |
4.0*4 |
1800 |
4 |
224000 |
10250 |
2750 |
2810 |
★Note: Design working condition parameters:
1. Inlet water temperature T1 = 37 ℃, outlet water temperature T2 = 32 ℃, water temperature drop △T = 5 ℃;
2. The inlet water pressure required by the cooling tower itself can be 3-6 meters of lift, that is, 0.03-0.06mpa;
3. Model description: F-square M-modular T-cooling tower
Previous
Next
Previous
none
Next
Your advice is our motivation
Related Products
FBN series countercurrent cooling tower type scope of application: working fluid temperature difference is large or high temperature (such as 65-35 ℃), such as melting furnace furnace, sintering furnace, vacuum furnace, air compressor, blast furnace, etc.
Cross-flow closed cooling towers are suitable for medium to large-scale cooling needs, and are especially suitable for applications that need to keep the water clean. They perform well in hot climates because they can use the cooling effect of outside air without requiring large amounts of water. They are usually used to cool hot water or cooling media in large facilities such as factories, power plants, chemical plants, refineries, steel plants, etc.
FBN series countercurrent cooling tower type scope of application: working fluid temperature difference is large or high temperature (such as 65-35 ℃), such as melting furnace furnace, sintering furnace, vacuum furnace, air compressor, blast furnace, etc.