Counterflow cooling tower
FBN series countercurrent cooling tower type scope of application: working fluid temperature difference is large or high temperature (such as 65-35 ℃), such as melting furnace furnace, sintering furnace, vacuum furnace, air compressor, blast furnace, etc.
Key words:
Classification:
Countercurrent
Tel:
Tel:
Counterflow cooling tower
Product Details
1. low temperature type: referring to inlet water temperature t1 = 37 ℃, outlet water temperature t2 = 32 ℃, temperature difference △t = 5 ℃
2. standard type: referring to inlet water temperature t1 = 38 ℃, outlet water temperature t2 = 32 ℃, temperature difference △t = 6 ℃
3. medium temperature type: referring to inlet water temperature t1 = 43 ℃, outlet water temperature t2 = 33 ℃, temperature difference △t = 10 ℃
4. high temperature type: referring to the inlet water temperature t1 = 60 ℃, the outlet water temperature t2 = 35 ℃, the temperature difference △t = 25 ℃
FBN series countercurrent cooling tower type scope of application: working fluid temperature difference is large or high temperature (such as 65-35 ℃), such as melting furnace furnace, sintering furnace, vacuum furnace, air compressor, blast furnace, etc.
FBN series countercurrent cooling tower is easy to install. It integrates condenser, cooling tower, circulating water pump, water pool and connecting water pipe. It adopts the standard assembly method of upper and lower boxes and is equipped with equipment base. In most cases, it does not need to make another foundation, but only needs to level the ground with sufficient bearing capacity. It can also be arranged on the roof and installed in the open air.
|
Model |
tonnage |
Working pressure (mpa) |
Working flow (m³/h) |
Pipe diameter |
Spray water pump |
Fan |
Host size (mm) |
||||
|
Power (kw) |
水量(m³/h) |
Power (kw) |
Air volume (m³/h) |
Long |
Wide |
High |
|||||
|
ML-FBN-10G/T |
10 |
0.15 |
10 |
DN50 |
0.75 |
10 |
0.37 |
10000 |
1530 |
910 |
2100 |
|
ML-FBN-20G/T |
20 |
0.2 |
20 |
DN50 |
1.1 |
20 |
0.37*2 |
10000 |
2300 |
910 |
2350 |
|
ML-FBN-30G/T |
30 |
0.2 |
30 |
DN65 |
1.1 |
30 |
0.75*2 |
10000 |
2300 |
1160 |
2400 |
|
ML-FBN-50G/T |
50 |
0.2 |
50 |
DN80 |
1.5 |
50 |
1.5*2 |
28000 |
2800 |
1160 |
2600 |
|
ML-FBN-80G/T |
80 |
0.25 |
80 |
DN80 |
2.2 |
80 |
2.2*2 |
29000 |
2900 |
1910 |
2650 |
|
ML-FBN-90G/T |
90 |
0.25 |
90 |
DN80 |
2.2 |
90 |
2.2*2 |
34000 |
2900 |
1910 |
2700 |
|
ML-FBN-100G/T |
100 |
0.3 |
100 |
DN100 |
2.2 |
100 |
2.2*2 |
34000 |
3300 |
1910 |
2700 |
|
ML-FBN-120G/T |
120 |
0.3 |
120 |
DN100 |
3 |
120 |
2.2*2 |
34000 |
3400 |
2200 |
2750 |
|
ML-FBN-150G/T |
150 |
0.35 |
150 |
DN125 |
3 |
150 |
2.2*4 |
22000 |
3400 |
2200 |
2850 |
|
ML-FBN-160G/T |
160 |
0.35 |
160 |
DN125 |
3 |
160 |
2.2*4 |
22000 |
3500 |
2300 |
2850 |
|
ML-FBN-180G/T |
180 |
0.4 |
180 |
DN150 |
4 |
180 |
2.2*4 |
34000 |
4000 |
2200 |
2800 |
|
ML-FBN-200G/T |
200 |
0.4 |
200 |
DN200 |
4 |
200 |
1.5*6 |
34000 |
4000 |
2300 |
3000 |
★Note: The unit size and number of coil connections on the sample may vary. The exact dimensions, number of coil connections and piping structure are detailed in the drawings provided by the factory.
Previous
Next
Previous
none
Next
Your advice is our motivation
Related Products
FBN series countercurrent cooling tower type scope of application: working fluid temperature difference is large or high temperature (such as 65-35 ℃), such as melting furnace furnace, sintering furnace, vacuum furnace, air compressor, blast furnace, etc.
Cross-flow closed cooling towers are suitable for medium to large-scale cooling needs, and are especially suitable for applications that need to keep the water clean. They perform well in hot climates because they can use the cooling effect of outside air without requiring large amounts of water. They are usually used to cool hot water or cooling media in large facilities such as factories, power plants, chemical plants, refineries, steel plants, etc.
FBN series countercurrent cooling tower type scope of application: working fluid temperature difference is large or high temperature (such as 65-35 ℃), such as melting furnace furnace, sintering furnace, vacuum furnace, air compressor, blast furnace, etc.